ATTRIBUTES
Motors:
Single speed in 2 and 4 poles, depending on the version.
Two speed in 4/8 poles.
IE3 efficiency category from 0,75kW onwards, IE2 minimum for lower kW motors.
IE4 efficiency category for motor powers from 75kW to 200kW.
Not applicable to 8 pole or two speed motors.
F300-120 & F400-120 motors are IP55, class H insulation.
Electrical supplies
Three phase 230/400V-50/60Hz up to 3 kW.
Three phase 380/415V-50Hz, for higher power motors and two speed motors.
Motors suitable for inverter control.
In emergency operation, no need for DOL or de-rating, as long as the VFTM range of VSDs is used, and/or requirements defined in EN 12101-3 are followed.
60Hz versions available in EasyVent.
Additional Information
Standard air direction Impeller-Motor (Form B).
Suitable for horizontal (B, A) or vertical (BD, AU) mounting installation.
Diameters 1250 with motor size IEC250 and above, 1400 and 1600 with long casing version come with pre-mounted support feet for horizontal installation.
Single speed motors in 6 poles.
Two speed motors in 2/4, 4/6 and 6/12 poles.
Air direction Motor-Impeller (Form A). (Not valid for 2 poles F400-120 version).
Reversible airflow version (AB).
Casing in stainless steel or paint finish.
Motors with PTC thermistor or heating resistors.

Motor approved S1 and S2
F400-120 and F300-120 certified motors approved for running continuously (S1) or for emergency operation (S2).

Corrosion resistance
Casings formed from rolled sheet steel with a corrosion resistant hot dip galvanised finish.

Motor support
Manufactured fromsheet steel with a corrosion resistant hot dip galvanised or Magnelis finish. Models from 400 to 800.

Aerodynamic motor support
Aerodynamic design of the motor support to optimise airflow performances models from 900 to 1250.

Motor support (1400 and 1600 mm diameter):
Welded on the fan casing. The whole assembly with a corrosion resistant hot dip galvanised finish.

Impeller dynamically balanced
According to ISO 1940 standard, providing vibration free operation.

Wide blade design higher pressure
Wide blade design to ensure the highest efficient airflow performances.

Terminal box
External terminal box to ease the electrical connection.